C5-05: ASR Limit
No.
Name
(Hex.)
C5-05
ASR Limit
(021F)
If the motor rated slip is high, it is necessary to increase the setting for correct motor speed control. Use U6-04 [ASR
Output] to make sure that ASR is operating at the limit set in this parameter. When ASR is operating at the limit,
correctly set the PG signal and these parameters before you make changes to C5-05.
• F1-01 [Encoder 1 Pulse Count (PPR)]
• F1-12 [Encoder 1 Gear Teeth 1]
• F1-13 [Encoder 1 Gear Teeth 2]
C5-06: ASR Delay Time
No.
Name
(Hex.)
C5-06
ASR Delay Time
(0220)
If you have a load with low rigidity or if oscillation is a problem, decrease C5-01 in 2-unit decrements or decrease
C5-06 in 0.001-unit decrements.
C5-07: ASR Gain Switchover Frequency
No.
Name
(Hex.)
C5-07
ASR Gain Switchover
Frequency
(0221)
Switching the proportional gain and integral time in the low or high speed range can help operation become stable. A
good switching point is 80% of the frequency where oscillation occurs or at 80% of the maximum output frequency.
Note:
An MFDI set for H1-xx = 77 [MFDI Function Selection = ASR Gain (C5-03) Select] will have priority over the ASR gain switching
frequency.
C5-08: ASR Integral Limit
No.
Name
(Hex.)
C5-08
ASR Integral Limit
(0222)
C5-12: Integral Operation @ Accel/Decel
No.
Name
(Hex.)
C5-12
Integral Operation @ Accel/
Decel
(0386)
When it is necessary for the motor speed to be as near the frequency reference as possible during acceleration or
deceleration, set this parameter to 1.
Note:
If you enable integral control, overshoot or undershoot can occur when acceleration or deceleration complete. If there are problems with
overshooting and undershooting, set this parameter to 0.
0 : Disabled
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
Set the ASR output limit as a percentage of E1-04 [Maximum Output Frequency].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the filter time constant of the torque reference output from the speed loop. Usually it is not
necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the frequency where the drive will switch between these parameters:
C5-01 and C5-03 [ASR Proportional Gain 1/2]
C5-02 and C5-04 [ASR Integral Time 1/2]
V/f
CL-V/f
OLV
CLV
AOLV
Set the upper limit of the ASR integral amount as a percentage of the rated load.
V/f
CL-V/f
OLV
CLV
AOLV
Sets ASR integral operation during acceleration and deceleration.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.4 C: Tuning
Default
(Range)
5.0%
(0.0 - 20.0%)
Default
(Range)
Determined by A1-02
(0.000 - 0.500 s)
Default
(Range)
Determined by A1-02
(Determined by A1-02)
Default
(Range)
400%
(0 - 400%)
Default
(Range)
0
(0, 1)