12.8 H: Terminal Functions
■
31: DWEZ Analog Input 2
Setting Value
Function
31
DWEZ Analog Input 2
■
32: DWEZ Analog Input 3
Setting Value
Function
32
DWEZ Analog Input 3
◆
H4: Analog Outputs
H4 parameters set the drive analog monitors. These parameters select monitor parameters, adjust gain and bias, and
select output signal levels.
■
Calibrate Meters Connected to MFAO Terminals FM and AM
To calibrate the meters connected to terminals FM and AM, use these parameters:
• H4-02 [Terminal FM Analog Output Gain]
• H4-03 [Terminal FM Analog Output Bias]
• H4-05 [Terminal AM Analog Output Gain]
• H4-06 [Terminal AM Analog Output Bias]
Set these parameters where the output voltage of 10 V and output current of 20 mA are 100% of the signal level. Use
jumper switch S5 and H4-07 [Terminal FM Signal Level Select] or H4-08 [Terminal AM Signal Level Select] to select
the voltage output and current output.
No.
H4-02
Terminal FM Analog Output Gain
H4-03
Terminal FM Analog Output Bias
H4-05
Terminal AM Analog Output Gain
H4-06
Terminal AM Analog Output Bias
H4-07
Terminal FM Signal Level Select
H4-08
Terminal AM Signal Level Select
Figure 12.110
and
Figure 12.111
942
V/f
CL-V/f
OLV
CLV
AOLV
Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
Name
show the gain and bias.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Range
-999.9 - +999.9%
-999.9 - +999.9%
-999.9 - +999.9%
-999.9 - +999.9%
0: 0 to 10 Vdc
1: -10 to +10 Vdc
2: 4 to 20 mA
0: 0 to 10 Vdc
1: -10 to +10 Vdc
2: 4 to 20 mA
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Default
100.0%
0.0%
50.0%
0.0%
0
0