12.8 H: Terminal Functions
31: DWEZ Analog Input 2
Setting Value
Function
31
DWEZ Analog Input 2
32: DWEZ Analog Input 3
Setting Value
Function
32
DWEZ Analog Input 3

H4: Analog Outputs

H4 parameters set the drive analog monitors. These parameters select monitor parameters, adjust gain and bias, and
select output signal levels.
Calibrate Meters Connected to MFAO Terminals FM and AM
To calibrate the meters connected to terminals FM and AM, use these parameters:
• H4-02 [Terminal FM Analog Output Gain]
• H4-03 [Terminal FM Analog Output Bias]
• H4-05 [Terminal AM Analog Output Gain]
• H4-06 [Terminal AM Analog Output Bias]
Set these parameters where the output voltage of 10 V and output current of 20 mA are 100% of the signal level. Use
jumper switch S5 and H4-07 [Terminal FM Signal Level Select] or H4-08 [Terminal AM Signal Level Select] to select
the voltage output and current output.
No.
H4-02
Terminal FM Analog Output Gain
H4-03
Terminal FM Analog Output Bias
H4-05
Terminal AM Analog Output Gain
H4-06
Terminal AM Analog Output Bias
H4-07
Terminal FM Signal Level Select
H4-08
Terminal AM Signal Level Select
Figure 12.110
and
Figure 12.111
942
V/f
CL-V/f
OLV
CLV
AOLV
Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
Name
show the gain and bias.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Range
-999.9 - +999.9%
-999.9 - +999.9%
-999.9 - +999.9%
-999.9 - +999.9%
0: 0 to 10 Vdc
1: -10 to +10 Vdc
2: 4 to 20 mA
0: 0 to 10 Vdc
1: -10 to +10 Vdc
2: 4 to 20 mA
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Default
100.0%
0.0%
50.0%
0.0%
0
0