YASKAWA GA800 Technical Reference page 969

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

Parameters for KEB Ride-Thru
Table 12.67
shows the parameters that adjust the KEB Ride-Thru function. Parameter settings are different for the
different KEB methods set in L2-29 [KEB Energy Backup Method].
No.
Name
C1-09
Fast Stop Time
C2-03
S-Curve Time @ Start of Decel • If ov occurs immediately after you start KEB deceleration, increase the setting
L2-05
Undervoltage Detection Lvl
(Uv1)
L2-06
Kinetic Energy Backup Decel
Time
L2-07
Kinetic Energy Backup Accel
Time
L2-08
Frequency Gain at KEB Start
L2-10
Minimum KEB Time
L2-11
KEB DC Bus Voltage Setpoint • Single Drive KEB Ride-Thru 2
L3-20
DC Bus Voltage Adjustment
Gain
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Figure 12.128 KEB Function Wiring Example
Table 12.67 Parameters for KEB Ride-Thru
Configuring Settings
• If ov [Overvoltage] occurs during KEB deceleration, increase the setting value.
• If Uv1 [DC Bus Undervoltage] occurs during KEB deceleration, decrease the
setting value.
value.
• If Uv1 occurs immediately after you start operation, decrease the setting value.
If Uv1 occurs immediately after you start KEB deceleration, increase the setting
value to detect power loss more quickly.
• Does KEB Tuning.
• If ov or Uv1 occur during KEB deceleration after the KEB Tuning, set L2-06 in
these conditions:
– If ov occurs, increase the setting value
– If Uv1 occurs, decrease the setting value.
Sets the acceleration time to return to the frequency reference value before a power
loss, after you cancel the KEB operation. When L2-07 = 0, the drive uses the
standard acceleration times set in C1-01, C1-03, C1-05, and C1-07 [Acceleration
Time].
• If ov occurs immediately after you start operation, decrease the setting value.
• If Uv1 occurs immediately after you start KEB deceleration, increase the setting
value.
• With KEB Ride-Thru
There is Uv1 because you set a digital input for KEB Ride-Thru and the device
that controls the input operated too slowly after power loss.
• Without KEB Ride-Thru
If the DC bus voltage overshoots immediately after KEB Ride-Thru starts,
increase L2-10 to longer than the overshoot.
Set to approximately 1.22 x input voltage.
• Single Drive KEB Ride-Thru 1, System KEB Ride-Thru 1, or System KEB Ride-
Thru 2
Set to approximately 1.4 x input voltage.
• If ov or Uv1 occurs at the start of deceleration when you use KEB operation,
increase this value in 0.1-unit increments.
• If there is torque ripple during deceleration when you use KEB Ride-Thru,
decrease the value.
12.9 L: Protection Functions
L2-29 [Kinetic Energy Backup Method]
0
1
2
*1
x
-
-
x
-
x
x
x
x
*2
-
-
x
x
x
x
x
x
-
x
x
x
x
x
x
x
-
x
-
3
-
x
x
*2
x
x
x
x
-
12
969