B.1 A: Initialization Parameters

B.1 A: Initialization Parameters
Symbol
V/f
V/f
Parameter is ONLY available when operating the drive with V/f control.
OLV
OLV
OLV
OLV
Parameter is ONLY available when operating the drive with Open Loop Vector control.
Parameter can be changed during run.
The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor
Control Method, Password, User Parameters and more.
u

A1: Initialization

No.
(Addr.
Name
Hex)
A1-00
(0100)
Language Selection
<1>
A1-01
(0101)
Access Level Selection
<2>
A1-03
Initialize Parameters
(0103)
A1-04
Password
(0104)
A1-05
Password Setting
(0105)
A1-06
Application Preset
(0127)
<1> Parameter setting value is not reset to the default value when the drive is initialized.
<2> Default setting value is dependent on the Initialization parameter A1-03.
256
Table B.1 Symbols and Icons Used in Parameter Descriptions
LCD Display
Select Language
0: English
0: English
1: Japanese
1:
(Japanese)
2: German
2: Deutsch
3: French
4: Italian
3: Français
4: Italiano
5: Spanish
6: Portuguese
5: Español
7: Chinese
6: Português
7:
0: View and set A1-01 and A1-04. Uo-oo parameters can also
Access Level
be viewed.
0: Operation Only
1: User Parameters (access to parameters selected by the user,
1: User Parameters
A2-01 to A2-32)
2: Advanced Level
2: Advanced Access (access to view and set all parameters)
3: Lock parameters
Init Parameters
0: No initialization
0: No Initialize
1110: User Initialize (parameter values must be stored using
1110: User Initialize
parameter o2-03)
2220: 2-Wire Initial
2220: 2-Wire initialization
3330: 3-Wire Initial
3330: 3-Wire initialization
5550: Term->Cntrl Int
5550: Terminal->Control Initialize
6008: Pressure Control
6008: Pressure Control
6009: Pump down level
6009: Pump down level
6010: Geothermal
6010: Geothermal mode
mode
6011: VTC pressure control
6011: VTC Pressure Ctl
7770: General purpose
7770: General purpose
When the value set into A1-04 does not match the value set into
Enter Password
A1-05, parameters A1-01 through A1-03 and A2-01 through A2-33
cannot be changed.
Select Password
0: General-purpose
Application Sel
8: Pressure control
0: General
9: Pump down level
8: Pressure Control
10: Geothermal mode
9: Pump Down Level
11: VTC pressure control
10: Geothermal Mode
Note:
11: VTC Pressure Ctl
Description
Description
This parameter is not settable. It is used as a
monitor only.
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
Values
Page
Default: 0
Range: 0 to 7
Default: 2
Range: 0 to 3
Default: 0
Range: 0 to 5550;
149
6008 to 6011;
7770
Default: 0000
Min.: 0000
Max.: 9999
Default: 0000
Min.: 0000
Max.: 9999
Default: 0
Range: 0; 8 to 11