7.2 A: Initialization Parameters

7.2

A: Initialization Parameters

A1: Initialization
No.
Name
(Hex.)
A1-00
Language Selection
(0100)
RUN
A1-01
Access Level Selection
(0101)
RUN
A1-03
Initialize Parameters
(0103)
A1-04
Password
(0104)
A1-05
Password Setting
(0105)
A1-06
Application Preset
(0127)
A1-11
Firmware Update Lock
(111D)
Expert
A1-12
Bluetooth ID
(1564)
A2: User Parameters
No.
Name
(Hex.)
A2-01
User Parameter 1
(0106)
A2-02
User Parameter 2
(0107)
A2-03
User Parameter 3
(0108)
A2-04
User Parameter 4
(0109)
A2-05
User Parameter 5
(010A)
174
Sets the language for the HOA keypad.
Note:
When you use A1-03 [Initialize Parameters] to initialize the drive, the drive will not reset this
parameter.
0 : English
5 : Spanish
Sets user access to parameters. The access level controls which parameters the keypad will display
and which parameters you can set.
0 : Operation Only
1 : User Parameters
2 : Advanced Level
3 : Expert Level
4 : Lock Parameters
Sets parameters to default values.
0 : No Initialization
1110 : User Initialization
2220 : 2-Wire Initialization
Entry point for the password set in A1-05 [Password Setting]. The user can view the settings of
parameters that are locked without entering the password. Enter the correct password in this
parameter to change parameter settings.
Sets a password to lock parameters and prevent changes to parameter settings. Enter the correct
password in A1-04 [Password] to unlock parameters and accept changes.
Sets the drive to operate in selected application conditions.
0 : No Preset Selected
1 : General Purpose Fan
2 : Fan w/ PID Control
3 : Return Fan w/ PID Control
4 : Cooling Tower Fan
5 : Cooling Tower Fan w/ PID
6 : Secondary Pump
7 : Pump w/ PID Control
Protects the drive firmware. When you enable the protection, you cannot update the drive firmware.
0 : Disabled
1 : Enabled
Sets the password necessary to use Bluetooth to control the drive with a smartphone or tablet.
Sets the parameter number to be shown for number 1 of the [User Custom Parameters] under the
main menu. You can select a maximum of 32 parameters for the drive and set them to parameters A2-
01 to A2-32.
Sets the parameter number to be shown for number 2 of the [User Custom Parameters] under the
main menu. You can select a maximum of 32 parameters for the drive and set them to parameters A2-
01 to A2-32.
Sets the parameter number to be shown for number 3 of the [User Custom Parameters] under the
main menu. You can select a maximum of 32 parameters for the drive and set them to parameters A2-
01 to A2-32.
Sets the parameter number to be shown for number 4 of the [User Custom Parameters] under the
main menu. You can select a maximum of 32 parameters for the drive and set them to parameters A2-
01 to A2-32.
Sets the parameter number to be shown for number 5 of the [User Custom Parameters] under the
main menu. You can select a maximum of 32 parameters for the drive and set them to parameters A2-
01 to A2-32.
YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
Description
Description
Default
(Range)
0
(0, 5)
2
(0 - 4)
0
(0, 1110, 2220)
0000
(0000 - 9999)
0000
(0000 - 9999)
0
(0 - 7)
0
(0, 1)
-
(0000 - 9999)
Default
(Range)
A1-02
(A1-00 - Z3-16)
b1-01
(A1-00 - Z3-16)
b1-02
(A1-00 - Z3-16)
b1-03
(A1-00 - Z3-16)
C1-01
(A1-00 - Z3-16)