Three-Phase Directional Overpower Protection 32O; Identification; Function Block; Functionality - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 4
Protection functions
4.4.3
4.4.3.1
4.4.3.2
4.4.3.3
4.4.3.4
352

Three-phase directional overpower protection 32O

Identification

Function description
Three-phase directional overpower
protection

Function block

32O
I3P
U3P
PICKUP
BLOCK
BLK_TRIP
BLK_PICKUP
FR_ TIMER
GUID-F3F299DA-FB9A-47F0-ADCE-B910F720E98C V1 EN
Figure 160:
Function block

Functionality

The directional overpower protection 32O can be used as generator protection against
delivering excessive power beyond its capacity to the grid, against generator running like
motor, against motor running like generator and protecting motor which consumes more
reactive power due to loss of field. It can also be used in feeder protection for indicating
overload on the distribution system, to indicate that a customer is supplying power into the
grid and for protecting the transformer from delivering an excessive load.
The function starts and operates when the measured power exceeds the set limit and in a
specified direction. The operate time characteristics are according to definite time (DT).
This function contains a blocking functionality. It is possible to block the function outputs,
timer or the function itself, if desired.

Operation principle

The function can be enabled and disabled with the Operation setting. The corresponding
parameter values are "Enable" and "Disable".
The operation of 32O can be described by using a module diagram. All the modules in the
diagram are explained in the next sections.
IEC 61850
identification
DOPPDPR
TRIP
1MAC504801-IB E
IEC 60617
ANSI/IEE C37.2
identification
device number
P>
32O
620 series ANSI
Technical Manual