ABB RELION 620 Series Technical Manual page 779

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
Section 10
10.1
10.1.1
10.1.1.1
10.1.1.2
620 series ANSI
Technical Manual
Recording functions
Disturbance recorder DFR
Functionality
The relay is provided with a disturbance recorder featuring up to 12 analog and 64 binary
signal channels. The analog channels can be set to record either the waveform or the trend
of the currents and voltages measured.
The analog channels can be set to trigger the recording function when the measured value
falls below or exceeds the set values. The binary signal channels can be set to start a
recording either on the rising or the falling edge of the binary signal or on both.
By default, the binary channels are set to record external or internal relay signals, for
example, the pickup or trip signals of the relay stages, or external blocking or control
signals. Binary relay signals, such as a protection pickup or trip signal, or an external relay
control signal via a binary input, can be set to trigger the recording. Recorded information
is stored in a non-volatile memory and can be uploaded for subsequent fault analysis.
Recorded analog inputs
The user can map any analog signal type of the protection relay to each analog channel of
the disturbance recorder by setting the Channel selection parameter of the corresponding
analog channel. In addition, the user can enable or disable each analog channel of the
digital fault recorder by setting the Operation parameter of the corresponding analog
channel to "Enable" or "Disable".
All analog channels of the disturbance recorder that are enabled and have a valid signal
type mapped are included in the recording.
Triggering alternatives
The recording can be triggered by any or several of the following alternatives:
Section 10
Recording functions
773