Section 6
Supervision functions
6.6.6
6.6.7
Table 445:
66/51LRS Group settings
Parameter
Values (Range)
Pickup detection A
0.1...10.0
Motor start-up A
1.0...10.0
Motor start-up time
1...80
Lock rotor time
2...120
Str over delay time
0...60000
620
Signals
Table 443:
66/51LRS Input signals
Name
Type
I_A
SIGNAL
I_B
SIGNAL
I_C
SIGNAL
BLOCK
BOOLEAN
BLK_LK_ST
BOOLEAN
CB_CLOSED
BOOLEAN
STALL_IND
BOOLEAN
ST_EMERG_ENA
BOOLEAN
Table 444:
66/51LRS Output signals
Name
Type
OPR_IIT
BOOLEAN
OPR_STALL
BOOLEAN
MOT_START
BOOLEAN
LOCK_START
BOOLEAN
Settings
Unit
Step
xIn
0.1
xIn
0.1
s
1
s
1
ms
1
Default
Description
0
Phase A current
0
Phase B current
0
Phase C current
0=False
Block of function
0=False
Blocks lock out condition for restart of motor
0=False
Input showing the status of motor circuit breaker
0=False
Input signal for showing the motor is not stalling
0=False
Enable emergency start to disable lock of start of motor
Description
Trip signal for thermal stress.
Trip signal for stalling protection.
Signal to show that motor startup is in progress
Lock out condition for restart of motor.
Default
Description
1.5
Current value for detecting starting of motor.
6
Motor starting current
10
Motor starting time
10
Permitted stalling time
100
Time delay to check for completion of motor
startup period
1MAC504801-IB E
620 series ANSI
Technical Manual