the different waveform and the different rate of change of the normal inrush current and
the inrush current containing the fault current. The algorithm does not eliminate the
blocking at inrush currents, unless there is a fault in the protected area.
The feature can be enabled and disabled through the Harmonic deblock 2.H setting.
Fifth harmonic blocking
The inhibition of the protection relay operation in situations of overexcitation is based on
the ratio of the fifth harmonic to the fundamental component of the differential current
(Id5f / Id1f). The ratio is calculated separately for each phase without weighting factors.
If the ratio exceeds the set value of Pickup value 5.H and blocking is enabled through the
Restraint mode setting, the operation of the biased stage of the protection relay in the
concerned phase is blocked.
At dangerous levels of overvoltage which may cause damage to the transformer, the
blocking can be automatically eliminated. The blocking is removed if the ratio of the fifth
harmonic to the fundamental component of the differential current exceeds the set value
of the Stop value 5.H setting, and the blocking removal is enabled. The enabling and
disabling of deblocking feature is done through the Harmonic deblock 5.H setting.
harmonic
content
Stop value 5 . H
hysteresis
Pickup value 5 . H
hysteresis
5 th harmonic block
GUID-764E7379-E8DF-4DD7-88A0-694558942F9D V1 EN
Figure 196:
The fifth harmonic blocking limits and the operation when both blocking
and deblocking features are enabled through the Harmonic deblock 5.H
setting
Fifth harmonic blocking has a hysteresis to avoid rapid fluctuation between TRUE and
FALSE. The required consecutive fulfillments of the condition can be counted using the
blocking counter. When the condition is not fulfilled, the counter is decreased (if >0).
Also fifth harmonic deblocking (based on the higher limit, Stop value 5.H, if enabled with
Harmonic deblock 5.H) has a hysteresis and a counter which counts the required
of
/ %
fundamental
1
0
Section 4
Protection functions
t
429