Section 4
Protection functions
Table 254:
24 Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Cooling time
5...10000
Constant delay
100...120000
Reset delay time
0...60000
Maximum trip time
500000...10000000
Minimum trip time
200...60000
Restart Ena level
0...100
Voltage selection
1=phase-to-earth
2=phase-to-phase
3=pos sequence
Phase selection
1=A or AB
2=B or BC
3=C or CA
Leakage React
0.0...50.0
Voltage Max Cont
80...160
4.2.6.9
312
Unit
Step
s
1
ms
10
ms
10
ms
10
ms
10
%
1
%
0.1
%
1

Monitored data

Table 255:
24 Monitored data
Name
Type
PICKUP_DUR
FLOAT32
T_ENARESTART
INT32
VOLTPERHZ
FLOAT32
24
Enum
Default
Description
5=disable
Operation Mode Disable/Enable
600
Time required to cool the machine
800
Parameter constant delay
100
Resetting time of the trip time counter in DT
mode
1000000
Maximum trip time for IDMT curves
200
Minimum trip time for IDMT curves
0
Determines the level in % when block restart is
released
3=pos sequence
Selection of phase / phase-to-phase / pos
sequence voltages
1=A or AB
Parameter for phase selection
0.0
Leakage reactance of the machine
110
Maximum allowed continuous operating
voltage ratio
Values (Range)
Unit
0.00...100.00
%
0...10000
s
0.00...10.00
pu
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
1MAC504801-IB E
Description
Ratio of pickup time / trip time
(in %)
Estimated time to reset of
block restart
Excitation level, i.e U/f ratio or
Volts/Hertz
Status
620 series ANSI
Technical Manual