Section 5
Protection-related functions
5.1.4
526
Operation principle
The function can be enabled and disabled with the Operation setting. The corresponding
parameter values are "Enable" and "Disable".
The operation of an inrush current detection function can be described using a module
diagram. All the modules in the diagram are explained in the next sections.
A070694 V2 EN
Figure 250:
Functional module diagram. I_1H and I_2H represent fundamental and
second harmonic values of phase currents.
I_2H/I_1H
This module calculates the ratio of the second harmonic (I_2H) and fundamental
frequency (I_1H) phase currents. The calculated value is compared to the set Pickup
value. If the calculated value exceeds the set Pickup value, the module output is activated.
Level detector
The output of the phase specific level detector is activated when the fundamental
frequency current I_1H exceeds five percent of the nominal current.
Timer
Once activated, the timer runs until the set Trip delay time value. The time characteristic
is according to DT. When the trip timer has reached the Trip delay time value, the BLK2H
output is activated. After the timer has elapsed and the inrush situation still exists, the
BLK2H signal remains active until the I_2H/I_1H ratio drops below the value set for the
ratio in all phases, that is, until the inrush situation is over. If the drop-off situation occurs
1MAC504801-IB E
620 series ANSI
Technical Manual