Section 4
Protection functions
4.1.3.10
186

Monitored data

Table 131:
67/51P Monitored data
Name
Type
PICKUP_DUR
FLOAT32
FAULT_DIR
Enum
DIRECTION
Enum
DIR_A
Enum
DIR_B
Enum
DIR_C
Enum
ANGLE_A
FLOAT32
ANGLE_B
FLOAT32
ANGLE_C
FLOAT32
67/51P
Enum
Table 132:
67/50P Monitored data
Name
Type
PICKUP_DUR
FLOAT32
FAULT_DIR
Enum
DIRECTION
Enum
Table continues on next page
Values (Range)
Unit
0.00...100.00
%
0=unknown
1=forward
2=backward
3=both
0=unknown
1=forward
2=backward
3=both
0=unknown
1=forward
2=backward
3=both
0=unknown
1=forward
2=backward
3=both
0=unknown
1=forward
2=backward
3=both
-180.00...180.00
deg
-180.00...180.00
deg
-180.00...180.00
deg
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Values (Range)
Unit
0.00...100.00
%
0=unknown
1=forward
2=backward
3=both
0=unknown
1=forward
2=backward
3=both
1MAC504801-IB E
Description
Ratio of pickup time / trip time
Detected fault direction
Direction information
Direction phase A
Direction phase B
Direction phase C
Calculated angle difference,
Phase A
Calculated angle difference,
Phase B
Calculated angle difference,
Phase C
Status
Description
Ratio of pickup time / trip time
Detected fault direction
Direction information
620 series ANSI