Section 6
Supervision functions
6.3.7
Table 430:
CCM Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Pickup value
0.05...0.20
Max alarm current
1.00...5.00
6.3.8
6.3.9
6.4
6.4.1
596
Settings
Unit
Step
xIn
0.01
xIn
0.01
Monitored data
Table 431:
CCM Monitored data
Name
Type
I_DIFF
FLOAT32
CCM
Enum
Technical data
Table 432:
CCM Technical data
Characteristic
1)
Trip time
1) Including the delay of the output contact
Advanced current circuit supervision for transformers
MCS 3I, I2
Identification
Function description
Advanced current circuit supervision for
transformers
Default
Description
1=enable
Operation Enable / Disable
0.05
Minimum trip current differential level
1.50
Block of the function at high phase current
Values (Range)
Unit
0.00...40.00
xIn
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Value
<30 ms
IEC 61850
IEC 60617
identification
identification
CTSRCTF
MCS 3I, I2
1MAC504801-IB E
Description
Differential current
Status
ANSI/IEEE C37.2
device number
MCS 3I, I2
620 series ANSI
Technical Manual