620 series ANSI
Technical Manual
A071272 V1 EN
Figure 378:
Autoreclosing sequence with two shots with different shot settings
according to initiation signal
t
Time delay of high-speed autoreclosing, here:
HSAR
t
Time delay of delayed autoreclosing, here:
DAR
t
Operating time for the 50P-1 protection stage to clear the fault
l>>
t
or
Operating time for the 51P or 51N/G protection stage to clear the fault
l>
lo>
t
Operating time for opening the circuit breaker
CB_O
t
Operating time for closing the circuit breaker
CB_C
In this case, the number of needed CBBs is three, that is, the first shot's reclosing time
depends on the initiation signal.
Section 9
Control functions
First reclose time
Second reclose time