Settings - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
4.7.2.7
Table 372:
78 Group settings
Parameter
Values (Range)
Oos trip mode
1=Way in
2=Way out
3=Adaptive
Forward Reach
0.00...6000.00
Reverse Reach
0.00...6000.00
Inner blinder R
1.00...6000.00
Outer blinder R
1.01...10000.00
Impedance angle
10.0...90.0
Zone 1 reach
1...100
Max number slips
1...10
Max num. slips zn2
1...20
Max num. slips zn3
1...20
Swing time
0...300000
Trip delay time
0...60000
Trip dropout time
0...60000
V dip time
500...5000
Zone 2 enable
1=Yes
0=No
Zone 3 enable
1=Yes
0=No
620 series ANSI
Technical Manual
Table 371:
78 Output signals
Name
Type
TRIP
BOOLEAN
SWING_TR
BOOLEAN
SWING
BOOLEAN
OSB
BOOLEAN
OSB_Z2
BOOLEAN

Settings

Unit
Step
ohm
0.01
ohm
0.01
ohm
0.01
ohm
0.01
deg
0.1
%
1
1
1
1
ms
10
ms
10
ms
10
ms
10
Description
OOS Trip
Swing trip output
Swing output
OOS block zone 1
OOS block zone 2
Default
Description
2=Way out
OOS trip mode
1000.00
Forward reach of mho circle
100.00
Reverse reach of mho circle
150.00
Inner blinder at R axis
400.00
Outer blinder at R axis
90.0
Angle of mho circle and blinders
70
Reach of zone 1 into mho circle
1
Number of pole slips before tripping zone 1
1
Number of pole slips before tripping zone 2
1
Number of pole slips before tripping zone 3
500
Time between blinders for swing
300
Delay after OOS trip detected
100
Time trip output remains active
2000
Voltage dip time
0=No
Enable zone 2 feature
0=No
Enable zone 3 feature
Section 4
Protection functions