Current based inverse definite minimum time
characteristics
IDMT curves for overcurrent protection
In inverse-time modes, the trip time depends on the momentary value of the current: the
higher the current, the faster the trip time. The trip time calculation or integration starts
immediately when the current exceeds the set Pickup value and the PICKUP output is
activated.
The TRIP output of the component is activated when the cumulative sum of the integrator
calculating the overcurrent situation exceeds the value set by the inverse-time mode. The
set value depends on the selected curve type and the setting values used. The curve scaling
is determined with the Time multiplier setting.
There are two methods to level out the inverse-time characteristic.
The Minimum operate time setting defines the minimum operating time for the IDMT
curve, that is, the operation time is always at least the Minimum operate time setting.
Alternatively, the IDMT Sat point is used for giving the leveling-out point as a
multiple of the Start value setting. (Global setting: Configuration/System/IDMT
Sat point). The default parameter value is 50. This setting affects only the overcurrent
and earth-fault IDMT timers.
IDMT operation time at currents over 50 x In is not guaranteed.