Monitored Data - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
Table 147:
50N/G-3 Group settings
Parameter
Values (Range)
Pickup value
1.00...40.00
Pickup value mult
0.8...10.0
Trip delay time
20...200000
Table 148:
50N/G-3 Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Reset delay time
0...60000
IG/I0 signal Sel
1=Measured IG
2=Calculated I0
4.1.4.10
620 series ANSI
Technical Manual
Unit
Step
xIn
0.01
0.1
ms
10
Unit
Step
ms
1

Monitored data

Table 149:
51N/G Monitored data
Name
Type
PICKUP_DUR
FLOAT32
51N/G
Enum
Table 150:
50N/G-1/2 Monitored data
Name
Type
PICKUP_DUR
FLOAT32
50N/G-1/2
Enum
Table 151:
50N/G-3 Monitored data
Name
Type
PICKUP_DUR
FLOAT32
50N/G-3
Enum
Default
Description
1.00
Pickup value
1.0
Multiplier for scaling the pickup value
20
Trip delay time
Default
Description
5=disable
Operation Disable / Enable
20
Reset delay time
1=Measured IG
Measured IG or calculated I0
Values (Range)
Unit
0.00...100.00
%
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Values (Range)
Unit
0.00...100.00
%
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Values (Range)
Unit
0.00...100.00
%
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Section 4
Protection functions
Description
Ratio of pickup time / trip time
Status
Description
Ratio of pickup time / trip time
Status
Description
Ratio of pickup time / trip time
Status
197