Signals; Series Ansi; Settings; Monitored Data - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 4
Protection functions
4.2.5.6
4.2.5.7
Table 245:
27PS Group settings
Parameter
Values (Range)
Pickup value
0.010...1.200
Trip delay time
40...120000
Voltage block value
0.01...1.00
Enable block value
0=False
1=True
Table 246:
27PS Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Reset delay time
0...60000
Relative hysteresis
1.0...5.0
4.2.5.8
294

Signals

Table 243:
27PS Input signals
Name
Type
V
SIGNAL
1
BLOCK
BOOLEAN
Table 244:
27PS Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN

Settings

Unit
Step
xUn
0.001
ms
10
xUn
0.01
Unit
Step
ms
1
%
0.1

Monitored data

Table 247:
27PS Monitored data
Name
Type
PICKUP_DUR
FLOAT32
27PS
Enum
Default
Description
0
Positive phase sequence voltage
0=False
Block signal for activating the blocking mode
Description
Trip
Pickup
Default
Description
0.500
Pickup value
40
Trip delay time
0.20
Internal blocking level
1=True
Enable Internal Blocking
Default
Description
5=disable
Operation Disable / Enable
20
Reset delay time
4.0
Relative hysteresis for operation
Values (Range)
Unit
0.00...100.00
%
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
1MAC504801-IB E
Description
Ratio of pickup time / trip time
Status

620 series ANSI

Technical Manual