Section 5
Protection-related functions
5.5.7
Table 407:
AFD Group settings
Parameter
Values (Range)
Phase pickup value
0.50...40.00
Ground pickup value
0.05...8.00
Operation mode
1=Light+current
2=Light only
3=BI controlled
Table 408:
AFD Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
5.5.8
5.5.9
556
Table 406:
AFD Output signals
Name
Type
TRIP
BOOLEAN
ARC_FLT_DET
BOOLEAN
Settings
Unit
Step
xIn
0.01
xIn
0.01
Unit
Step
Monitored data
Table 409:
AFD Monitored data
Name
Type
AFD
Enum
Technical data
Table 410:
AFD Technical data
Characteristic
Operation accuracy
Trip time
Operation mode = "Light
only"
Reset time
Reset ratio
Description
Trip
Fault arc detected=light signal output
Default
Description
2.50
Operating phase current
0.20
Operating residual current
1=Light+current
Operation mode
Default
Description
1=enable
Operation Disable / Enable
Values (Range)
Unit
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Value
±3% of the set value or ±0.01 × I
Minimum
9 ms
<40 ms
Typically 0.96
1MAC504801-IB E
Description
Status
n
Typical
Maximum
10 ms
12 ms
620 series ANSI
Technical Manual