Settings - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
4.5.2.7
Table 321:
49T Group settings
Parameter
Values (Range)
Env temperature Set
-50...100
Current reference
0.05...4.00
Temperature rise
0.0...200.0
Maximum temperature
0.0...200.0
Trip temperature
80.0...120.0
Alarm temperature
40.0...100.0
Reclose temperature
40.0...100.0
Short time constant
6...60000
Long time constant
60...60000
Weighting factor p
0.00...1.00
Table 322:
49T Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Initial temperature,
0.0...100.0
percent value
620 series ANSI
Technical Manual
Table 320:
49T Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
ALARM
BOOLEAN
BLK_CLOSE
BOOLEAN

Settings

Unit
Step
°C
1
xIn
0.01
°C
0.1
°C
0.1
%
0.1
%
0.1
%
0.1
s
1
s
1
0.01
Unit
Step
%
0.1
Description
Trip
Pickup
Thermal Alarm
Thermal overload indicator. To inhibite reclose.
Default
Description
40
Ambient temperature used when no external
temperature measurement available
1.00
The load current leading to Temperature raise
temperature
78.0
End temperature rise above ambient
105.0
Temperature level for trip
100.0
Trip temperature, percent value
90.0
Alarm temperature, percent value
60.0
Temperature for reset of block reclose after trip
450
Short time constant in seconds
7200
Long time constant in seconds
0.40
Weighting factor of the short time constant
Default
Description
5=disable
Operation Disable / Enable
80.0
Temperature raise at startup
Section 4
Protection functions
387