Application

When a motor runs with a load connected, it draws a current equal to a value between the
no-load value and the rated current of the motor. The minimum load current can be
determined by studying the characteristics of the connected load. When the current drawn
by the motor is less than the minimum load current drawn, it can be inferred that the motor
is either disconnected from the load or the coupling mechanism is faulty. If the motor is
allowed to run in this condition, it may aggravate the fault in the coupling mechanism or
harm the personnel handling the machine. Therefore, the motor has to be disconnected
from the power supply as soon as the above condition is detected.
37M detects the condition by monitoring the current values and helps disconnect the
motor from the power supply instantaneously or after a delay according to the
requirement.
When the motor is at standstill, the current will be zero and it is not recommended to
activate the trip during this time. The minimum current drawn by the motor when it is
connected to the power supply is the no load current, that is, the higher pickup value
current. If the current drawn is below the lower pickup value current, the motor is
disconnected from the power supply. 37M detects this condition and interprets that the
motor is de-energized and disables the function to prevent unnecessary trip events.

Signals

Table 198:
37M Input signals
Name
Type
I_A
SIGNAL
I_B
SIGNAL
I_C
SIGNAL
BLOCK
BOOLEAN
Table 199:
37M Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
Default
Description
0
Phase A current
0
Phase B current
0
Phase C current
0=False
Block all binary outputs by resetting timers
Description
Trip
Pickup
Section 4
Protection functions
257