Settings - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
4.1.1.9
Table 98:
51P Group settings
Parameter
Values (Range)
Pickup value
0.05...5.00
Pickup value mult
0.8...10.0
Time multiplier
0.05...15.00
Table continues on next page
620 series ANSI
Technical Manual
Table 94:
50P-3 Input signals
Name
Type
I_A
SIGNAL
I_B
SIGNAL
I_C
SIGNAL
BLOCK
BOOLEAN
ENA_MULT
BOOLEAN
Table 95:
51P Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
Table 96:
50P-1/2 Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
Table 97:
50P-3 Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN

Settings

Unit
Step
xIn
0.01
0.1
0.01
Default
Description
0
Phase A current
0
Phase B current
0
Phase C current
0=False
Block signal for activating the blocking mode
0=False
Enable signal for current multiplier
Description
Trip
Pickup
Description
Trip
Pickup
Description
Trip
Pickup
Default
Description
1
Pickup value
1.0
Multiplier for scaling the pickup value
1.00
Time multiplier in IEC/ANSI IDMT curves
Section 4
Protection functions
153