ABB RELION 620 Series Technical Manual page 535

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
5.1.7
Table 386:
INR Group settings
Parameter
Values (Range)
Pickup value
5...100
Trip delay time
20...60000
Table 387:
INR Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Reset delay time
0...60000
5.1.8
5.1.9
620 series ANSI
Technical Manual
Settings
Unit
Step
%
1
ms
1
Unit
Step
ms
1
Monitored data
Table 388:
INR Monitored data
Name
Type
INR
Enum
Technical data
Table 389:
INR Technical data
Characteristic
Operation accuracy
Reset time
Reset ratio
Trip time accuracy
Protection-related functions
Default
Description
20
Ratio of the 2. to the 1. harmonic leading to
restraint
20
Trip delay time
Default
Description
5=disable
Operation Disable / Enable
20
Reset delay time
Values (Range)
Unit
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Value
At the frequency f = f
Current measurement:
±1.5% of the set value or ±0.002 × I
Ratio I2f/I1f measurement:
±5.0% of the set value
+35 ms / -0 ms
Typically 0.96
20 ms / -10 ms
Section 5
Description
Status
n
n
529