ABB RELION 620 Series Technical Manual page 698

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 8
Power quality measurement functions
Parameter
Values (Range)
VVa swell time 1
0.5...54.0
Voltage swell set 2
100.0...140.0
VVa swell time 2
10.0...80.0
Voltage swell set 3
100.0...140.0
VVa swell time 3
2000...60000
Voltage Int set
0.0...100.0
VVa Int time 1
0.5...30.0
VVa Int time 2
10.0...180.0
VVa Int time 3
2000...60000
VVa Dur Max
100...3600000
Table 521:
PQSS Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Phase supervision
1=Ph A
2=Ph B
3=Ph A + B
4=Ph C
5=Ph A + C
6=Ph B + C
7=Ph A + B + C
Phase mode
1=Three Phase
2=Single Phase
Variation enable
1=Swell
2=Dip
3=Swell + dip
4=Interruption
5=Swell + Int
6=Dip + Int
7=Swell+dip+Int
8.3.9
692
Unit
Step
cycles
0.1
%
0.1
cycles
0.1
%
0.1
ms
10
%
0.1
cycles
0.1
cycles
0.1
ms
10
ms
100
Unit
Step
Monitored data
Table 522:
PQSS Monitored data
Name
Type
ST_A
BOOLEAN
ST_B
BOOLEAN
ST_C
BOOLEAN
Table continues on next page
Default
Description
0.5
Voltage variation swell duration 1
120.0
Swell limit 2 in % of reference voltage
10.0
Voltage variation swell duration 2
120.0
Swell limit 3 in % of reference voltage
2000
Voltage variation swell duration 3
10.0
Interruption limit in % of reference voltage
3.0
Voltage variation Int duration 1
30.0
Voltage variation Int duration 2
3000
Voltage variation interruption duration 3
60000
Maximum voltage variation duration
Default
Description
5=disable
Operation Disable / Enable
7=Ph A + B + C
Monitored voltage phase
2=Single Phase
Three/Single phase mode
7=Swell+dip+Int
Enable variation type
Values (Range)
Unit
0=False
1=True
0=False
1=True
0=False
1=True
1MAC504801-IB E
Description
Pickup Phase A (Voltage
Variation Event in progress)
Pickup Phase B (Voltage
Variation Event in progress)
Pickup Phase C (Voltage
Variation Event in progress)
620 series ANSI
Technical Manual