Section 4
Protection functions
4.5.3.6
402
175
Negative Seq factor =
2
5 7
.
GUID-DF682702-E6B1-4814-8B2E-31C28F3A03DF V1 EN
Setting the thermal restart level
The restart disable level can be calculated as follows:
startup time of the motor
θ i
=
100
%
operate time when no prior load
GUID-5B3B714D-8C58-4C5D-910D-A23852BC8B15 V1 EN
For example, the motor startup time is 11 seconds, start-up current 6 x rated and Time
constant start is set for 800 seconds. Using the trip curve with no prior load, the operation
time at 6 x rated current is 25 seconds, one motor startup uses 11/25 ≈ 45 percent of the
thermal capacity of the motor. Therefore, the restart disable level must be set to below 100
percent - 45 percent = 55 percent, for example to 50 percent (100 percent - (45 percent +
margin), where margin is 5 percent).
Setting the thermal alarm level
Tripping due to high overload is avoided by reducing the load of the motor on a prior
alarm.
The value of Alarm thermal value is set to a level which allows the use of the full thermal
capacity of the motor without causing a trip due to a long overload time. Generally, the
prior alarm level is set to a value of 80 to 90 percent of the trip level.

Signals

Table 327:
49M Input signals
Name
Type
I_A
SIGNAL
I_B
SIGNAL
I_C
SIGNAL
I2
SIGNAL
BLOCK
BOOLEAN
START_EMERG
BOOLEAN
TEMP_AMB
FLOAT32
5 4
.
=
×
10
0 0 % +
margin
Default
Description
0
Phase A current
0
Phase B current
0
Phase C current
0
Negative sequence current
0=False
Block signal for activating the blocking mode
0=False
Signal for indicating the need for emergency start
0
The ambient temperature used in the calculation
1MAC504801-IB E
(Equation 31)
620 series ANSI
Technical Manual