Section 4
Protection functions
4.1.2.8
Table 112:
51LT Group settings
Parameter
Values (Range)
Pickup value
0.05...5.00
Pickup value mult
0.8...10.0
Time multiplier
1.00...15.00
Trip delay time
40...200000
Operating curve type
1=LT Ext Inv
2=LT Very Inv
3=LT Inv
4=LT Mod Inv
5=Long DT
6=Very LT Ext Inv
7=Very LT Very Inv
8=Very LT Inv
9=LT Normal Inv
14=IEC LT Inv
17=Programmable
Type of reset curve
1=Immediate
2=Def time reset
3=Inverse reset
Table 113:
51LT Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Num of pickup phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
Minimum trip time
20...60000
Reset delay time
0...60000
Measurement mode
1=RMS
2=DFT
3=Peak-to-Peak
Curve parameter A
0.0086...120.0000
Curve parameter B
0.0000...0.7120
Table continues on next page
162
Table 111:
51LT Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN

Settings

Unit
Step
xIn
0.01
0.1
0.01
ms
10
Unit
Step
ms
1
ms
1
Description
Trip
Pickup
Default
Description
2
Pickup value
1.0
Multiplier for scaling the pickup value
1.00
Time multiplier in IEC/ANSI IDMT curves
40
Trip delay time
5=Long DT
Selection of time delay curve type
1=Immediate
Selection of reset curve type
Default
Description
5=disable
Operation Disable / Enable
1=1 out of 3
Number of phases required for trip activation
20
Minimum trip time for IDMT curves
20
Reset delay time
2=DFT
Selects used measurement mode
28.2000
Parameter A for customer programmable
curve
0.1217
Parameter B for customer programmable
curve
1MAC504801-IB E
620 series ANSI
Technical Manual