620 series ANSI
Technical Manual
Loss of phase 37
Identification
Function description
Phase undercurrent protection
Function block
GUID-ED7916D7-8083-4660-B274-252DA7DCB833-ANSI V1 EN
Figure 120:
Function block
Functionality
The phase undercurrent protection 37 is used to detect an undercurrent that is considered
as a fault condition.
37 picks up when the current is less than the set limit. Operation time characteristics are
according to definite time (DT).
The function contains a blocking functionality. It is possible to block function outputs and
reset the definite timer if desired.
Operation principle
The function can be enabled and disabled with the Operation setting. The corresponding
parameter values are "Enable" and "Disable".
The operation of the phase undercurrent protection can be described with a module
diagram. All the modules in the diagram are explained in the next sections.
IEC 61850
IEC 60617
identification
identification
PHPTUC1
3I<
Section 4
Protection functions
ANSI/IEEE C37.2
device number
37
263