Table 62:
GOOSERCV_INTL Output signals
Name
Type
OP
BOOLEAN
CL
BOOLEAN
OK
BOOLEAN
VALID
BOOLEAN

GOOSERCV_CMV function block

Function block

GUID-4C3F3A1A-F5D1-42E1-840F-6106C58CB380 V1 EN
Figure 45:
Function block

Functionality

The GOOSERCV_CMV function is used to connect GOOSE measured value inputs to the
application. The MAG_IN (amplitude) and ANG_IN (angle) inputs are defined in the
GOOSE configuration (PCM600).
The MAG output passes the received GOOSE (amplitude) value for the application.
Default value (0) is used if VALID output indicates invalid status.
The ANG output passes the received GOOSE (angle) value for the application. Default
value (0) is used if VALID output indicates invalid status.

Signals

Table 63:
GOOSERCV_CMV Input signals
Name
Type
MAG_IN
FLOAT32
ANG_IN
FLOAT32
Basic functions
Description
Position open output signal
Position closed output signal
Position OK output signal
Output signal
Default
Description
0
Input signal (amplitude)
0
Input signal (angle)