Section 6
Supervision functions
6.5.6
6.5.7
Table 440:
60 Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Neg Seq current Lev
0.03...0.20
Neg Seq voltage Lev
0.03...0.20
Current change rate
0.01...0.50
Voltage change rate
0.50...0.90
Change rate enable
0=False
1=True
Min Op voltage delta
0.01...1.00
Table continues on next page
608
Signals
Table 438:
60 Input signals
Name
Type
I_A
SIGNAL
I_B
SIGNAL
I_C
SIGNAL
I
SIGNAL
2
V_A_AB
SIGNAL
V_B_BC
SIGNAL
V_C_CA
SIGNAL
V
SIGNAL
2
BLOCK
BOOLEAN
CB_CLOSED
BOOLEAN
DISCON_OPEN
BOOLEAN
MINCB_OPEN
BOOLEAN
Table 439:
60 Output signals
Name
Type
FUSEF_3PH
BOOLEAN
FUSEF_V
BOOLEAN
Settings
Unit
Step
xIn
0.01
xVn
0.01
xIn
0.01
xVn
0.01
xVn
0.01
Default
Description
0
Phase A current
0
Phase B current
0
Phase C current
0
Negative sequence current
0
Phase A voltage
0
Phase B voltage
0
Phase C voltage
0
Negative phase sequence voltage
0=False
Block of function
0=False
Active when circuit breaker is closed
0=False
Active when line disconnector is open
0=False
Active when external MCB opens protected voltage
circuit
Description
Three-phase pickup of function
General pickup of function
Default
Description
5=disable
Operation Disable / Enable
0.03
Trip level of neg seq undercurrent element
0.10
Trip level of neg seq overvoltage element
0.15
Trip level of change in phase current
0.60
Trip level of change in phase voltage
0=False
Enabling operation of change based function
0.70
Minimum trip level of phase voltage for delta
calculation
1MAC504801-IB E
620 series ANSI
Technical Manual