ABB RELION 620 Series Technical Manual page 321

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
620 series ANSI
Technical Manual
V_A_AB
Level
V_B_BC
detector
V_C_CA
BLOCK
GUID-1F833D04-EA04-427E-BC3D-2BFE5E694FFC V1 EN
Figure 143:
Functional module diagram
Level detector
The fundamental frequency component of the measured three-phase voltages over the
range of 10...70 Hz is compared phase-wise to the set Pickup value . If the measured value
is lower than the set value of the Pickup value setting, the Level detector enables the phase
selection logic module. The Relative hysteresis setting can be used for preventing
unnecessary oscillations if the input signal slightly varies above or below the Pickup value
setting. After leaving the hysteresis area, the pickup condition has to be fulfilled again and
it is not sufficient for the signal to only return back to the hysteresis area.
The Voltage selection setting is used for selecting the phase-to-earth or phase-to-phase
voltages for protection.
Phase selection logic
If the fault criteria are fulfilled in the Level detector, the phase selection logic detects the
phase or phases in which the fault level is detected. If the number of faulty phases match
with the set Num of pickup phases, the phase selection logic activates the Timer.
Timer
Once activated, the Timer activates the PICKUP output. The time characteristic is definite
time only.
When the trip timer has reached the value set by Trip delay time, the TRIP output is
activated.
In a drop-off situation, that is, when a fault suddenly disappears before the trip delay is
exceeded, the reset state is activated. The reset timer runs until the set Reset delay time
value is exceeded. If the drop-off situation exceeds the set Reset delay time, the Timer is
reset and the PICKUP output is deactivated.
Blocking logic
There are three operation modes in the blocking functionality. The operation modes are
controlled by the BLOCK input and the global setting Configuration/System/Blocking
mode which selects the blocking mode. The BLOCK input can be controlled by a binary
Timer
Phase
selection
t
logic
Blocking
logic
Section 4
Protection functions
TRIP
PICKUP
315

Advertisement

Table of Contents
loading

Table of Contents