1MAC504801-IB E
11.5
11.5.1
11.5.2
11.5.3
11.5.4
620 series ANSI
Technical Manual
Generic control points CNTRL
Identification
Function description
Generic control points
Function block
GUID-C2A6026C-1E8D-4382-9675-2C63E413998B V1 EN
Figure 410:
Function block
Functionality
The generic control points function block CNTRL can be used in combination with other
function blocks such as FKEYGGIO. SPC offers the capability to activate its outputs
through a local or remote control. The local control is provided through the buttons in the
front panel and the remote control is provided through communications. CNTRL has two
modes of operation. In the "Toggle" mode, the block toggles the output signal for every
input pulse received. In the "Pulsed" mode, the block generates an output pulse of a preset
duration.
Operation principle
The function can be enabled and disabled with the Operation setting. The corresponding
parameter values are "Enable" and "Disable".
IEC 61850
IEC 60617
identification
identification
SPCGGIO
SPC
Section 11
Other functions
ANSI/
IEEEidentification
CNTRL
801