Figure 227:
High-impedance busbar differential protection with different CT burden
value on each feeder
First, the stabilizing voltage, that is, the voltage appearing across the measuring branch
during the out-of-zone fault, is calculated assuming that one of the CTs connected in
parallel is fully saturated. The stabilizing voltage can be calculated using the formula:
I
k
max
(
)
U
R
R
=
+
s
in
m
n
GUID-6A4C58E7-3D26-40C9-A070-0D99BA209B1A V1 EN
I
the highest through-fault current in primary amps. The highest earth-fault or short circuit current during
kmax
the out-of-zone fault.
n
the turns ratio of the CT
R
the secondary winding resistance of the CT in ohms
in
Section 4
Protection functions
(Equation 55)
479