Section 4
Protection functions
4.1.11.7
Table 200:
37M Group settings
Parameter
Values (Range)
Pickup value low
0.01...0.50
Pickup value high
0.01...1.00
Trip delay time
400...600000
Table 201:
37M Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Reset delay time
0...60000
4.1.11.8
4.1.11.9
258

Settings

Unit
Step
xIn
0.01
xIn
0.01
ms
10
Unit
Step
ms
1

Monitored data

Table 202:
37M Monitored data
Name
Type
PICKUP_DUR
FLOAT32
37M
Enum

Technical data

Table 203:
37M Technical data
Characteristic
Operation accuracy
Pickup time
Reset time
Reset ratio
Retardation time
Trip time accuracy in definite time mode
Default
Description
0.10
Current setting/Pickup value low
0.50
Current setting/Pickup value high
2000
Trip delay time
Default
Description
1=enable
Operation Disable / Enable
20
Reset delay time
Values (Range)
Unit
0.00...100.00
%
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Value
Depending on the frequency of the measured
current: f
±2 Hz
n
±1.5% of the set value or ±0.002 × I
Typically 300 ms
<40 ms
Typically 1.04
<35 ms
±1.0% of the set value or ±20 ms
1MAC504801-IB E
Description
Ratio of pickup time / trip time
Status
n
620 series ANSI
Technical Manual