Section 4
Protection functions
Parameter
Values (Range)
Curve Sat Relative
0.0...3.0
Voltage selection
1=phase-to-earth
2=phase-to-phase
Relative hysteresis
1.0...5.0
4.2.1.9
4.2.1.10
274
Unit
Step
0.1
%
0.1

Monitored data

Table 221:
59 Monitored data
Name
Type
PICKUP_DUR
FLOAT32
59
Enum

Technical data

Table 222:
59 Technical data
Characteristic
Operation accuracy
1)2)
Pickup time
V
value
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time mode
Operate time accuracy in inverse time mode
Suppression of harmonics
Pickup value = 1.0 × V
1)
, Voltage before fault = 0.9 × V
n
nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
2) Includes the delay of the signal output contact
Pickup value = 1.20 × V
3) Maximum
Default
2.0
2=phase-to-phase
4.0
Values (Range)
0.00...100.00
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Value
Depending on the frequency of the measured
voltage: f
±1.5% of the set value or ±0.002 × V
Minimum
Pickup
= 1.1 × set
23 ms
Fault
<40 ms
Depends on the set
<35 ms
±1.0% of the set value or ±20 ms
±5.0% of the theoretical value or ±20 ms
DFT: -50 dB at f = n × f
, f
n
n
Pickup value multiples in range of 1.10...2.00
,
n
1MAC504801-IB E
Description
Tuning parameter to avoid curve
discontinuities
Parameter to select phase or phase-to-phase
voltages
Relative hysteresis for operation
Unit
Description
%
Ratio of pickup time / trip time
Status
±2 Hz
n
Typical
27 ms
Relative hysteresis
, where n = 2, 3, 4, 5,...
n
= 60 Hz, overvoltage in one phase-to-phase with
n
Maximum
30 ms
3)
620 series ANSI
Technical Manual