Fault Records - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 3
Basic functions
3.7
82
Table 38:
SG operation mode = "Logic mode 2"
BI_SG_2
BI_SG_3
FALSE
FALSE
TRUE
FALSE
any
TRUE
any
any
any
any
any
any
The setting group 1 can be copied to any other or all groups from HMI (Copy group 1).

Fault records

The protection relay has the capacity to store the records of 128 latest fault events. Fault
records include fundamental or RMS current values. The records enable the user to
analyze recent power system events. Each fault record (FLTRFRC) is marked with an up-
counting fault number and a time stamp that is taken from the beginning of the fault.
The fault recording period begins from the pickup event of any protection function and
ends if any protection function trips or the pickup(s) is restored before the trip event. If a
pickup is restored without a trip event, the pickup duration shows the protection function
that has picked up first.
Pickup duration that has the value of 100% indicates that a protection function has tripped
during the fault and if none of the protection functions has been tripped, Pickup duration
shows always values less than 100%.
The Fault recorded data Protection and Pickup duration is from the same protection
function. The Fault recorded data trip time shows the time of the actual fault period.
The Trip time in the fault record is calculated based on the pickup and trip time stamps.
Pickup events may be delayed to avoid false positive reporting. Therefore, the Trip time
may be shorter than expected.
If some functions in relay application are sensitive to start frequently it
might be advisable to set the setting parameter Trig mode to "From trip".
Then only faults that cause an trip event trigger a new fault recording.
The fault-related current, voltage, frequency, angle values, shot pointer and the active
setting group number are taken from the moment of the operate event, or from the
Input
BI_SG_4
BI_SG_5
FALSE
any
FALSE
any
FALSE
any
TRUE
FALSE
TRUE
TRUE
TRUE
any
1MAC504801-IB E
BI_SG_6
Active group
any
1
any
2
any
3
FALSE
4
FALSE
5
TRUE
6
620 series ANSI
Technical Manual