1MAC504801-IB E
620 series ANSI
Technical Manual
GUID-93ECF983-CCBB-4277-8E7B-7EC43743A375 V1 EN
Figure 135:
Functional module diagram
V/f calculation
This module calculates the V/f ratio, that is, the excitation level from the internal induced
voltage (E) and frequency. The actual measured voltage (V
induced voltage (emf) E, a value the equipment has to withstand. This voltage
compensation is based on the load current (I
equipment. The leakage reactance of the transformer or generator is set through the
Leakage React setting in percentage of the Z base.
The internal induced voltage (E) is calculated from the measured voltage. The settings
Voltage selection and Phase supervision determine which voltages and currents are to be
used. If the Voltage selection setting is set to "phase-to-ground" or "phase-to-phase", the
Phase supervision setting is used for determining which phases or phase-to-phase
voltages ("A or AB", "B or BC" and "C or CA") and currents are to be used for the
calculation of the induced voltage.
Table 249:
Voltages and currents used for induced voltage (emf) E calculation
Voltage selection setting Phase supervision
setting
phase-to-ground
A or AB
phase-to-ground
B or BC
phase-to-ground
C or CA
phase-to-phase
A or AB
Table continues on next page
Protection functions
) deviates from the internal
m
) and the leakage reactance (X
L
Calculation of internal induced voltage (emf) E
(
E
3
V
I
(
j X
=
×
+
×
×
A
A
GUID-B567E82F-DDAB-4D87-A209-097D5FC072C6 V2 EN
(
E
3
V
I
(
j X
=
×
+
×
×
B
B
GUID-551F8B8A-40D2-4D99-B20D-6FC433406EFF V2 EN
(
E
V
I
j X
3
(
=
×
+
×
×
C
C
GUID-8B274F07-54A0-4CEC-9AAC-618F742D9EED V2 EN
(
E V
(
I
I
) (
j X
=
+
×
×
AB
A
B
GUID-BA2D5CDB-BC06-4F7E-A71F-A2BEFC10F5A2 V2 EN
Section 4
) of the
leak
1)
)
)
leak
)
)
leak
)
)
leak
)
)
leak