Section 7
Measurement functions
7.1.5.4
Table 470:
VA, VB, VC Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Measurement mode
1=RMS
2=DFT
Num of phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
V high high limit
0.00...4.00
V high limit
0.00...4.00
V low limit
0.00...4.00
V low low limit
0.00...4.00
V deadband
100...100000
7.1.5.5
644
Table 469:
VA, VB, VC Output signals
Name
Type
HIGH_ALARM
BOOLEAN
HIGH_WARN
BOOLEAN
LOW_WARN
BOOLEAN
LOW_ALARM
BOOLEAN
Settings
Unit
Step
xVn
xVn
xVn
xVn
Monitored data
Table 471:
VA, VB, VC Monitored data
Name
Type
VAB-kV
FLOAT32
VBC-kV
FLOAT32
VCA-kV
FLOAT32
Description
High alarm
High warning
Low warning
Low alarm
Default
Description
1=enable
Operation Disable / Enable
2=DFT
Selects used measurement mode
1=1 out of 3
Number of phases required by limit supervision
2
High alarm voltage limit
2
High warning voltage limit
0.00
Low warning voltage limit
0.00
Low alarm voltage limit
10000
Deadband configuration value for integral
calculation. (percentage of difference between
min and max as 0,001 % s)
Values (Range)
Unit
0.00...4.00
xVn
0.00...4.00
xVn
0.00...4.00
xVn
1MAC504801-IB E
Description
Measured phase to phase
voltage amplitude phase AB
Measured phase to phase
voltage amplitude phase BC
Measured phase to phase
voltage amplitude phase CA
620 series ANSI
Technical Manual