1MAC504801-IB E
9.2.7
620 series ANSI
Technical Manual
Example 1
The protection operation time is 0.5 seconds, the Fourth delay in SOTF parameter is set
to "1" and the Str 2 delay shot 4 parameter is 0.05 seconds. The protection pickup signal
is connected to the DEL_INIT_2 input.
If the protection picks up after the circuit breaker closes, the fast trip follows after the set
0.05 seconds. The total trip time is the protection pickup delay + 0.05 seconds + the time
it takes to open the circuit breaker.
Signals
Table 540:
79 Input signals
Name
Type
INIT_1
BOOLEAN
INIT_2
BOOLEAN
INIT_3
BOOLEAN
INIT_4
BOOLEAN
INIT_5
BOOLEAN
INIT_6
BOOLEAN
DEL_INIT_2
BOOLEAN
DEL_INIT_3
BOOLEAN
DEL_INIT_4
BOOLEAN
BLK_RECL_T
BOOLEAN
BLK_RCLM_T
BOOLEAN
BLK_THERM
BOOLEAN
CB_POS
BOOLEAN
CB_READY
BOOLEAN
INC_SHOTP
BOOLEAN
INHIBIT_RECL
BOOLEAN
RECL_ON
BOOLEAN
SYNC
BOOLEAN
Default
Description
0=False
AR initialization / blocking signal 1
0=False
AR initialization / blocking signal 2
0=False
AR initialization / blocking signal 3
0=False
AR initialization / blocking signal 4
0=False
AR initialization / blocking signal 5
0=False
AR initialization / blocking signal 6
0=False
Delayed AR initialization / blocking signal 2
0=False
Delayed AR initialization / blocking signal 3
0=False
Delayed AR initialization / blocking signal 4
0=False
Blocks and resets reclose time
0=False
Blocks and resets reclaim time
0=False
Blocks and holds the reclose shot from the thermal
overload
0=False
Circuit breaker position input
1=True
Circuit breaker status signal
0=False
A zone sequence coordination signal
0=False
Interrupts and inhibits reclosing sequence
0=False
Level sensitive signal for allowing (high) / not allowing
(low) reclosing
0=False
Synchronizing check fulfilled
Section 9
Control functions
745