Settings; Monitored Data - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
4.4.2.7
Table 289:
32N Group settings
Parameter
Values (Range)
Release delay time
0...1000
Directional mode
1=Non-directional
2=Forward
3=Reverse
Characteristic angle
-179...180
Max forward angle
0...180
Min forward angle
0...180
Max reverse angle
0...180
Min reverse angle
0...180
Table 290:
32N Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Reset delay time
0...60000
Min trip current
0.01...1.00
Min trip voltage
0.01...1.00
Pol reversal
0=False
1=True
IG/I0 Sel
1=Measured IG
2=Calculated I0
Pol signal Sel
1=Measured VG
2=Calculated V0
3=Neg. seq. volt.
4.4.2.8
620 series ANSI
Technical Manual

Settings

Unit
Step
ms
10
deg
1
deg
1
deg
1
deg
1
deg
1
Unit
Step
ms
1
xln
0.01
xVn
0.01

Monitored data

Table 291:
32N Monitored data
Name
Type
ANGLE_RCA
FLOAT32
32N
Enum
Default
Description
10
Release delay time
2=Forward
Directional mode
60
Characteristic angle
88
Maximum phase angle in forward direction
88
Minimum phase angle in forward direction
88
Maximum phase angle in reverse direction
88
Minimum phase angle in reverse direction
Default
Description
5=disable
Operation Disable / Enable
20
Reset delay time
0.10
Minimum trip current
0.30
Minimum trip voltage
0=False
Rotate polarizing quantity
2=Calculated I0
IG/I0 selection
2=Calculated V0
Selection for used polarization signal
Values (Range)
Unit
-180.00...180.00
deg
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Section 4
Protection functions
Description
Angle between operating
angle and characteristic angle
Status
351