Monitored Data; Ground Directional Power Protection 32N; Identification; Function Block - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
Table 283:
32P Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Reset delay time
0...60000
Min trip current
0.01...1.00
Min trip voltage
0.01...1.00
4.4.1.8
4.4.2
4.4.2.1
4.4.2.2
620 series ANSI
Technical Manual
Unit
Step
ms
1
xIn
0.01
xVn
0.01

Monitored data

Table 284:
32P Monitored data
Name
Type
ANGLE_RCA
FLOAT32
32P
Enum

Ground directional power protection 32N

Identification

Function description
Ground directional power protection

Function block

GUID-DCCE78B9-9984-4C66-A320-7C6F89243C3A-ANSI V1 EN
Figure 154:
Function block
Default
Description
5=disable
Operation Disable / Enable
20
Reset delay time
0.10
Minimum trip current
0.30
Minimum trip voltage
Values (Range)
Unit
-180.00...180.00
deg
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
IEC 61850
IEC 60617
identification
identification
DNZSRDIR
I2->, Io->
Section 4
Protection functions
Description
Angle between polarizing and
operating quantity
Status
ANSI/IEEE C37.2
device number
32N
343