1MAC504801-IB E
4.2.1.8
Table 219:
59 Group settings
Parameter
Values (Range)
Pickup value
0.05...1.60
Time multiplier
0.05...15.00
Trip delay time
40...300000
Operating curve type
5=ANSI DT
15=IEC DT
17=Inv. Curve A
18=Inv. Curve B
19=Inv. Curve C
20=Programmable
Type of reset curve
1=Immediate
2=Def time reset
-1=DT Lin decr rst
Table 220:
59 Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Num of pickup phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
Minimum trip time
40...60000
Reset delay time
0...60000
Curve parameter A
0.005...200.000
Curve parameter B
0.50...100.00
Curve parameter C
0.0...1.0
Curve parameter D
0.000...60.000
Curve parameter E
0.000...3.000
Table continues on next page
620 series ANSI
Technical Manual
Table 218:
59 Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN

Settings

Unit
Step
xVn
0.01
0.01
ms
10
Unit
Step
ms
1
ms
1
Description
Trip
Pickup
Default
Description
1.10
Pickup value
1.00
Time multiplier in IEC/ANSI IDMT curves
40
Trip delay time
5=ANSI DT
Selection of time delay curve type
1=Immediate
Selection of reset curve type
Default
Description
5=disable
Operation Disable / Enable
1=1 out of 3
Number of phases required for trip activation
40
Minimum trip time for IDMT curves
20
Reset delay time
1.000
Parameter A for customer programmable
curve
1.00
Parameter B for customer programmable
curve
0.0
Parameter C for customer programmable
curve
0.000
Parameter D for customer programmable
curve
1.000
Parameter E for customer programmable
curve
Section 4
Protection functions
273