Settings - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 4
Protection functions
4.4.5.7
Table 308:
55 Group settings
Parameter
Values (Range)
Dir pickup value
1=Lagging
2=Leading
Dir pickup reset value
1=Lagging
2=Leading
Dir alarm value
1=Lagging
2=Leading
Dir alarm reset value
1=Lagging
2=Leading
Pickup value
-0.99...0.99
Pickup reset value
-0.99...0.99
Alarm value
-0.99...0.99
Alarm reset value
-0.99...0.99
Trip delay time
100...300000
Alarm delay time
100...300000
Table 309:
55 Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Current block value
0.05...0.65
Voltage block value
0.05...0.50
Reset delay time
0...60000
Disable time
0...60000
Voltage reversal
0=No
1=Yes
372
Table 307:
55 Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
ALARM
BOOLEAN

Settings

Unit
Step
0.01
0.01
0.01
0.01
ms
1
ms
1
Unit
Step
xIn
0.01
xUn
0.01
ms
1
ms
Description
Trip
Pickup
Alarm
Default
Description
1=Lagging
PF direction for pickup value
1=Lagging
PF direction for pickup reset value
1=Lagging
PF direction for alarm value
1=Lagging
PF direction for alarm reset value
0.80
Pickup value
0.85
Value at which pickup resets, drops out
0.85
Alarm pickup value
0.90
Value at which alarm resets, drops out
500
Time delay for operation
500
Time delay for alarm
Default
Description
5=disable
Operation Disable / Enable
0.10
Current block value (minimum operating
current)
0.10
Voltage block value (minimum operating
voltage)
20
Reset delay time
5000
Additional time for which function is disabled
after removal of DISABLE input
0=No
Rotates the PF by 180 degrees
1MAC504801-IB E