Section 4
Protection functions
4.3.1.6
4.3.1.7
Table 267:
81 Group settings
Parameter
Values (Range)
Trip mode
1=Freq<
2=Freq>
3=df/dt
4=Freq< + df/dt
5=Freq> + df/dt
6=Freq< OR df/dt
7=Freq> OR df/dt
Pickup value Freq>
0.900...1.200
Pickup value Freq<
0.800...1.100
Pickup value df/dt
-0.200...0.200
Trip Tm Freq
80...200000
Trip Tm df/dt
120...200000
326
smaller power systems where the loss of a large generator requires quick remedial actions
to secure the power system integrity. In such situations, the load shedding actions are
required at a rather high frequency level. However, in combination with a large negative
frequency gradient, the underfrequency protection can be used at a high setting.

Signals

Table 265:
81 Input signals
Name
Type
F
SIGNAL
dF/dt
SIGNAL
BLOCK
BOOLEAN
Table 266:
81 Output signals
Name
Type
TRIP
BOOLEAN
OPR_OFRQ
BOOLEAN
OPR_UFRQ
BOOLEAN
OPR_FRG
BOOLEAN
PICKUP
BOOLEAN
ST_OFRQ
BOOLEAN
ST_UFRQ
BOOLEAN
ST_FRG
BOOLEAN

Settings

Unit
Step
xFn
0.001
xFn
0.001
xFn /s
0.005
ms
10
ms
10
Default
Description
0
Measured frequency
0
Rate of change of frequency
0=False
Block signal for activating the blocking mode
Description
Trip
Trip signal for overfrequency
Trip signal for underfrequency
Trip signal for frequency gradient
Pickup
Pickup signal for overfrequency
Pickup signal for underfrequency
Pickup signal for frequency gradient
Default
Description
1=Freq<
Frequency protection trip mode selection
1.050
Frequency pickup value overfrequency
0.950
Frequency pickup value underfrequency
0.010
Frequency pickup value rate of change
200
Trip delay time for frequency
400
Trip delay time for frequency rate of change
1MAC504801-IB E
620 series ANSI
Technical Manual