Section 12
General function block features
12.3.1.1
866
Standard inverse-time characteristics for overvoltage protection
The trip times for the standard overvoltage IDMT curves are defined with the coefficients
A, B, C, D and E.
The inverse trip time can be calculated with the formula:
k A
⋅
t s
=
−
>
V V
B
×
−
C
V
>
GUID-6E9DC0FE-7457-4317-9480-8CCC6D63AB35-ANSI V1 EN
t [s] trip time in seconds
V
measured voltage
Pickup value
V>
the set value of
Time multiplier
k
the set value of
Table 615:
Curve coefficients for the standard overvoltage IDMT curves
Curve name
A
(17) Inverse Curve A
1
(18) Inverse Curve B
480
(19) Inverse Curve C
480
+
D
E
B
C
1
32
32
1MAC504801-IB E
D
0
0
0.5
0.035
0.5
0.035
(Equation 112)
E
1
2
3
620 series ANSI
Technical Manual