Settings - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 4
Protection functions
4.1.3.9
Table 127:
67/51P Group settings
Parameter
Values (Range)
Pickup value
0.05...5.00
Pickup value mult
0.8...10.0
Time multiplier
0.05...15.00
Trip delay time
40...200000
Table continues on next page
182
Table 124:
67/50P Input signals
Name
Type
I_A
SIGNAL
I_B
SIGNAL
I_C
SIGNAL
I
SIGNAL
2
V_A_AB
SIGNAL
V_B_BC
SIGNAL
V_C_CA
SIGNAL
V
SIGNAL
1
V
SIGNAL
2
BLOCK
BOOLEAN
ENA_MULT
BOOLEAN
NON_DIR
BOOLEAN
Table 125:
67/51P Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
Table 126:
67/50P Output signals
Name
Type
PICKUP
BOOLEAN
TRIP
BOOLEAN

Settings

Unit
Step
xIn
0.01
0.1
0.01
ms
10
Default
Description
0
Phase A current
0
Phase B current
0
Phase C current
0
Negative phase sequence current
0
Phase to ground voltage A or phase to phase voltage AB
0
Phase to ground voltage B or phase to phase voltage BC
0
Phase to ground voltage C or phase to phase voltage
CA
0
Positive phase sequence voltage
0
Negative phase sequence voltage
0=False
Block signal for activating the blocking mode
0=False
Enable signal for current multiplier
0=False
Forces protection to non-directional
Description
Trip
Pickup
Description
Pickup
Trip
Default
Description
1
Pickup value
1.0
Multiplier for scaling the pickup value
1.00
Time multiplier in IEC/ANSI IDMT curves
40
Trip delay time
1MAC504801-IB E
620 series ANSI
Technical Manual