ABB RELION 620 Series Technical Manual page 583

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
6.1.8
6.1.9
620 series ANSI
Technical Manual
Monitored data
Table 421:
52CM Monitored data
Name
Type
T_TRV_OP
FLOAT32
T_TRV_CL
FLOAT32
T_SPR_CHR
FLOAT32
NO_OPR
INT32
INA_DAYS
INT32
CB_LIFE_A
INT32
CB_LIFE_B
INT32
CB_LIFE_C
INT32
IPOW_A
FLOAT32
IPOW_B
FLOAT32
IPOW_C
FLOAT32
52CM
Enum
Technical data
Table 422:
52CM Technical data
Characteristic
Current measuring accuracy
Operate time accuracy
Travelling time measurement
Values (Range)
Unit
0...60000
ms
0...60000
ms
0.00...99.99
s
0...99999
0...9999
-9999...9999
-9999...9999
-9999...9999
0.000...30000.00
0
0.000...30000.00
0
0.000...30000.00
0
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Value
±1.5% or ±0.002 x I
(at currents in the range of 0.1...10 x I
±5.0%
(at currents in the range of 10...40 x I
±1.0% of the set value or ±20 ms
+10 ms / -0 ms
Section 6
Supervision functions
Description
Travel time of the CB during
opening operation
Travel time of the CB during
closing operation
The charging time of the CB
spring
Number of CB operation cycle
The number of days CB has
been inactive
CB Remaining life phase A
CB Remaining life phase B
CB Remaining life phase C
Accumulated currents power
(Iyt), phase A
Accumulated currents power
(Iyt), phase B
Accumulated currents power
(Iyt), phase C