Section 3
Basic functions
68
Table 30:
Warning indications and codes
Warning indication
Warning code
Warning
System warning
Warning
Watchdog reset
Warning
Power down det.
Warning
IEC61850 error
Warning
Modbus error
Warning
DNP3 error
Warning
Dataset error
Warning
Report cont. error
Warning
GOOSE contr. error
Warning
SCL config error
Warning
Logic error
Warning
SMT logic error
Warning
GOOSE input error
ACT error
Warning
GOOSE Rx. error
Warning
AFL error
Warning
Unack card comp.
Warning
Protection comm.
Warning
ARC1 cont. light
Warning
ARC2 cont. light
Warning
ARC3 cont. light
Warning
RTD card error,X105
Table continues on next page
Additional information
2
An internal system error has occurred.
10
A watchdog reset has occurred.
11
The auxiliary supply voltage has dropped
too low.
20
Error when building the IEC 61850 data
model
21
Error in the Modbus communication
22
Error in the DNP3 communication
24
Error in the Data set(s)
25
Error in the Report control block(s)
26
Error in the GOOSE control block(s)
27
Error in the SCL configuration file or the file
is missing
28
Too many connections in the configuration
29
Error in the SMT connections
30
Error in the GOOSE connections
31
Error in the ACT connections
32
Error in the GOOSE message receiving
33
Analog channel configuration error
40
A new composition has not been
acknowledged/accepted.
50
Error in protection communication
85
A continuous light has been detected on
the ARC light input 1.
86
A continuous light has been detected on
the ARC light input 2.
87
A continuous light has been detected on
the ARC light input 3.
90
Temporary error occurred in RTD card
located in slot X105