ABB RELION 620 Series Technical Manual page 545

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MAC504801-IB E
5.2.6
5.2.7
Table 392:
50BF Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Current value
0.05...2.00
Current value Res
0.05...1.00
CB failure trip mode
1=2 out of 4
2=1 out of 3
3=1 out of 4
CB failure mode
1=Current
2=Breaker status
3=Both
CB fail retrip mode
1=Disabled
2=Without Check
3=Current check
Retrip time
0...60000
CB failure delay
0...60000
Table continues on next page
620 series ANSI
Technical Manual
Signals
Table 390:
50BF Input signals
Name
Type
I_A
SIGNAL
I_B
SIGNAL
I_C
SIGNAL
I_N
SIGNAL
BLOCK
BOOLEAN
PICKUP
BOOLEAN
POSCLOSE
BOOLEAN
CB_FAULT
BOOLEAN
Table 391:
50BF Output signals
Name
Type
CB_FAULT_AL
BOOLEAN
TRBU
BOOLEAN
TRRET
BOOLEAN
Settings
Unit
Step
xIn
0.05
xIn
0.05
ms
10
ms
10
Protection-related functions
Default
Description
0
Phase A current
0
Phase B current
0
Phase C current
0
Ground current
0=False
Block CBFP operation
0=False
CBFP pickup command
0=False
CB in closed position
0=False
CB faulty and unable to trip
Description
Delayed CB failure alarm
Backup trip
Retrip
Default
Description
1=enable
Operation Disable / Enable
0.30
Operating phase current
0.30
Operating residual current
2=1 out of 3
Backup trip current check mode
1=Current
Operating mode of function
1=Disabled
Operating mode of retrip logic
20
Delay timer for retrip
150
Delay timer for backup trip
Section 5
539