1MAC504801-IB E
Section 3
3.1
Table 7:
Analog input settings, phase currents
Parameter
Values (Range)
Secondary current
2=1A
3=5A
Primary current
1.0...6000.0
Amplitude corr. A
0.900...1.100
Amplitude corr. B
0.900...1.100
Amplitude corr. C
0.900...1.100
Nominal Current
39...4000
Reverse polarity
0=False
1=True
Table 8:
Analog input settings, residual current
Parameter
Values (Range)
Secondary current
1=0.2A
2=1A
3=5A
Primary current
1.0...6000.0
Amplitude corr.
0.900...1.100
Reverse polarity
0=False
1=True
Table 9:
Analog input settings, phase voltages
Parameter
Values (Range)
Primary voltage
0.100...440.000
Secondary voltage
60...210
VT connection
1=Wye
2=Delta
3=U12
4=UL1
Amplitude corr. A
0.900...1.100
Table continues on next page
620 series ANSI
Technical Manual
Basic functions

General parameters

Unit
Step
A
0.1
0.001
0.001
0.001
A
1
Unit
Step
A
0.1
0.001
Unit
Step
kV
0.001
V
1
0.001
Default
Description
3=5A
Rated secondary current
600.0
Rated primary current
1.000
Phase A amplitude correction factor
1.000
Phase B amplitude correction factor
1.000
Phase C amplitude correction factor
1300
Network Nominal Current (In)
0=False
Reverse the polarity of the phase CTs
Default
Description
2=1A
Secondary current
120
Primary current
1.000
Amplitude correction
0=False
Reverse the polarity of the residual CT
Default
Description
20.000
Primary rated voltage
100
Secondary rated voltage
2=Delta
Wye, delta, U12 or UL1 VT connection
1.000
Phase A Voltage phasor magnitude correction
of an external voltage transformer
Section 3
Basic functions
55