Settings - ABB RELION 620 Series Technical Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

Section 4
Protection functions
4.1.9.8
Table 188:
46M Group settings
Parameter
Values (Range)
Pickup value
0.01...0.50
Operating curve type
5=ANSI DT
15=IEC DT
17=Inv. Curve A
18=Inv. Curve B
Machine time Mult
5.0...100.0
Trip delay time
100...120000
Table 189:
46M Non group settings
Parameter
Values (Range)
Operation
1=enable
5=disable
Rated current
0.30...2.00
Maximum trip time
500000...7200000
Minimum trip time
100...120000
Cooling time
5...7200
Reset delay time
0...60000
250
Table 187:
46M Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
BLK_RESTART
BOOLEAN

Settings

Unit
Step
xIn
0.01
0.1
ms
10
Unit
Step
xIn
0.01
ms
1000
ms
1
s
1
ms
1
Description
Trip
Pickup
Overheated machine reconnection blocking
Default
Description
0.20
Pickup value
5=ANSI DT
Selection of time delay curve type
5.0
Machine related time constant
1000
Trip delay time
Default
Description
5=disable
Operation Disable / Enable
1.00
Rated current (Ir) of the machine (used only in
the IDMT)
1000000
Max trip time regardless of the inverse
characteristic
100
Minimum trip time for IDMT curves
50
Time required to cool the machine
20
Reset delay time
1MAC504801-IB E
620 series ANSI
Technical Manual